24
confIguratIon
61. Power reports - on change
This parameter determines the minimum change in consumed
power that will result in sending new power report to the main
controller.
For loads under 50W the parameter is not relevant and reports are
sent every 5W change.
Power report are sent no often then every 30 seconds.
Parameter size 2B
Default value 15 (15%)
Available
values
0 - reports are disabled
1-500 (1-500%) - change in power
62. Power reports - periodic
This parameter determines in what time intervals the periodic
power reports are sent to the main controller. Periodic reports do
not depend of power change (parameter 61).
Parameter size 2B
Default value 3600 (1h)
Available
values
0 - periodic reports are disabled
1-32400 (1-32400s) - report interval
63. Analog inputs reports - on change
This parameter denes minimal change (from the last reported) of
analog input value that results in sending new report.
Parameter is relevant only for analog inputs (parameter 20, 21, 22
or 23 set to 0 or 1).
Parameter size 1B
Default value 5 (0.5V)
Available
values
0 - reporting on change disabled
1-100 (0.1-10V, 0.1V step)
64. Analog inputs reports - periodic
This parameter denes reporting period of analog inputs value.
Periodical reports are independent from changes in value (param-
eter 63).
Parameter is relevant only for analog inputs (parameter 20, 21, 22
or 23 set to 0 or 1).
Parameter size 2B
Default value 0 (periodical reports disabled)
Available
values
0 – periodical reports disabled
60-32400 (60s-9h, 1s step)