134 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Operating Instructions Time Functions: Real-Time Clock
Automatic Test Operation
An automatic test of an addressable detector is performed each minute, resulting in a complete SLC
loop test in approximately 5 hours (if the loop has the maximum number of devices installed). The
detectors sensing chamber and electronics are functionally tested for normal, safe operation. A
trouble message is displayed upon failure of this test. A System Reset will clear this trouble.
Type Code Supervision
The FACP monitors addressable hardware device codes at slow intervals. Mismatch of any type
code, compared to the system program, will cause a device trouble.
System Alarm Verification
The control panel may be programmed to perform alarm verification to help eliminate the nuisance
of false alarms. Alarm verification applies to smoke detectors only.
Smoke Detector Data
Smoke detector data is monitored by the FACP, eliminating the need to test the sensitivity of each
detector at its location. A printout of each detectors data can be retrieved from the FACP using an
optional printer or Windows
©
HyperTerminal. Detector sensing ability can decrease with age and
should be monitored as part of a system’s routine maintenance.
4.15 Time Functions: Real-Time Clock
The FACP includes a crystal-based clock that provides time of day, date and day of week. Time is
displayed as 12 or 24 hour time with month/day/year and is stored in RAM. Daylight savings time
change-over is programmable and automatic. If both AC and battery are lost, the time must be
reset.
4.16 NAC Operation
There are up to four programmable NACs (Notification Appliance Circuits) resident on the FACP
main circuit board. The NACs may be programmed as silenceable or nonsilenceable and may also
be programmed for steady or coded operation. Coded operation provides a choice between March
Time, Temporal, California coding and two-stage operation.
4.17 Synchronized NAC Operation
Synchronization is a panel feature that controls the activation of notification appliances in such a
way that all devices will turn on and off at exactly the same time. This is particularly critical when
activating strobes which must be synchronized to avoid random activation and a potential hazard or
confusion. The FACP can be programmed to operate with a variety of manufacturers devices.
Important: When a Notification Appliance Circuit with a mix of audible and visual devices is pro-
grammed for silenceable and the synchronization feature is selected, only the audible devices will
be turned off if the Silence key is pressed. The visual devices (strobes, etc.) will continue to oper-
ate.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fire-Lite MS-9600LS and is the answer not in the manual?

Fire-Lite MS-9600LS Specifications

General IconGeneral
BrandFire-Lite
ModelMS-9600LS
CategoryControl Panel
LanguageEnglish

Related product manuals