132 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Operating Instructions Process Monitor Operation
4.7 Process Monitor Operation
Process Monitor operation will initiate the following events:
The piezo sounder pulses ¼ second On and ¼ second Off
The LCD displays a process monitor message along with the device name, type, address,
adjective/noun, associated zones and time/date
Relays programmed for process monitoring will be activated
The alarm relay is not
activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Process Monitor condition must be Acknowledged before the FACP can be reset
Note that, like supervisories, process monitor signals latch (except when programmed for process
monitor autoresettable) and can be assigned to software zones.
4.8 Hazard Condition Operation
Hazard Condition operation will initiate the following events:
The piezo sounder turns on steady
The LCD displays a hazard message along with the device name, type, address,
adjective/noun, associated zones and time/date
Relays programmed for process monitoring will be activated
The alarm relay is not
activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Hazard condition must be Acknowledged before the FACP can be reset
Hazard conditions latch and will therefore clear only when the hazard condition is cleared and the
panel reset. They can be assigned to software zones.
4.9 Medical Alert Condition Operation
Medical Alert Condition operation will initiate the following events:
The piezo sounder turns on steady
The LCD displays a medical alert message along with the device name, type, address,
adjective/noun, associated zones and time/date
Relays programmed for medical alert will be activated
The alarm relay is not
activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Medical Alert condition must be Acknowledged before the FACP can be reset
Medical alert conditions latch and will therefore clear only when the medical alert condition is
cleared and the panel reset. They can be assigned to software zones.