44
If a new alarm from the same detector or the activation of
another sensor in the same zone occurs within 30 minutes,
the alarm of fire panel is triggered.
In this phase the keypad and keys have the following
functions:
Alphanumeric keypad
No function is related to the alphanumeric keypad.
Cursor keys
Table 42: Cursor key functions in smoke delay
ESC and ENTER keys
Table 43: ESC and ENTER key function in smoke delay
Use to delete the operation and
return to the previous screen
Use to accept the selection and
activate the programming screen
DELAY TO ALARM
For each zone, you can program the activation of a
common delay to alarm delay of 9 minutes. The procedure
and the functionality of the cursors, ESC, and ENTER
keys are the same as the SMOKE DELAY parameters.
See Figure 27, d.
Figure 27: Programming option delay detector alarm
verification
If blinking, control panel working
properly
Name of selected control panel
DLY ALARM TIME (min)
If ON is selected for the option Delay to Alarm you can enter
the zone relevant delay to alarm time. The possible value
ranges from 0 (no delay) to 9 minutes. The value may be
incremented or decremented in steps of 1 minute using the
Up or Down keys.
4 Key – output
The output option, the 4 key in the programming menu,
activates the panel on the board output programming
screen. Use the output option to select the type of panel on
the board output, followed by the programming procedure
for that output. See Figure 24, 0.
Choose output
In this phase the keypads and the keys have the
following functions: