The FC410DDM provides the ability to connect and
interface 2 zones of 20 VDC 2-wire conventional fire
detectors, or two 4-20 mA signaling sensors, to the
FireClass fire alarm controller. The FC410DDM monitors
the status of the detectors and the wiring to the detectors
and signals detector and wiring status back to the
controller. The conventional detector circuits can be
configured to monitor 1 or 2 Class B spur circuits. The
4-20 mA signaling sensors may be one of two types:
Current sinking
Current sourcing
FC410QMO Quad monitored output module
The FC410QMO module comprises of four relays with
selectable wiring supervision.
The output wiring is monitored for any short or open circuit.
Spur and Loop configurations are supported.
The module has an integral loop isolator. If it activates, a
yellow LED illuminates. The activation remains in place
until the short is removed.
FC410QRM Quad relay module
The module provides four voltage free relay changeover
outputs. The outputs are monitored with parallel contacts
of the relays. Connect the outputs to an auxiliary voltage
source to monitor its voltage. Additionally, all the outputs
are configurable to the high voltage relay (HVR) mode,
which allows you to connect up to four HVR800 modules
for switching. For example 240 V loads galvanically
isolated.
The module has an integral loop isolator. If the integral
loop isolator activates a yellow LED illuminates. A yellow
LED illuminates when the integral loop isolator activates.
The activation remains in place until the short is removed.
Maximum relay current: 2 A
Maximum relay voltage: 30 V
FC410QIO Quad input output module
The module provides 4 monitored digital inputs and 4
potential free relay changeover outputs.The outputs are
monitored with parallel contacts of the relays. The
outputs can be connected to an auxiliary voltage source
and the voltage can be monitored. Additionally, all the
outputs can be connected to the HVR800, for switching
high power galvanic isolated loads. For more details refer
to the HVR800 documentation. The module has an
integral loop isolator. If this activates, a yellow LED
illuminates. The activation remains in place until the short
is removed. The digital input monitoring and isolator
functions are both configurable.
Maximum relay current: 2 A
Maximum relay voltage: 30 V
FC440SB Addressable Base Sounder
The visual indicating device (VID) sounder-beacons
and sounders are loop powered units driven from an
addressable controller panel. Set the tone and volume
in the FireClass FC500 (FC501_FC503_FC506)
Console.
Selectable flash rates are:
a) 1 Hz (flash every second)
b) 0.5 Hz (flash every 2 seconds)
The visual indicating device sounder-beacons are
available in ceiling and wall mounted variants, including
an outdoor wall version. The FC440SB variants are:
FC440SW
FC440SR
FC445SR
FC440AIW
FC440AIR
FC445AIR
FC440AIB
FC440AVB Addressable Sounder Base
VAD Sounder
The visual alarm device (VAD) sounder-beacons are
loop powered units driven from an addressable
controller panel. All VADs have a built-in two port loop
short circuit isolator.
Configure the settings for tones, volume, beacon flash,
and status monitoring using the control panel.
The VADs are available in ceiling and wall mounted
variants, including an outdoor wall version. The
FC440AVB variants are:
FC440AVW
FC440AVR
FC445AVR
FC445CAV
FC440AVB
FC441AVB
FC440CAVB