FC410LI Line isolator module
The FC410LI line isolator module is designed to be used
on the FC addressable controller loop circuits. It monitors
the line condition and when detecting a short circuit will
isolate the affected section while allowing the rest of the
addressing circuit to function normally.
The purpose of the FC410LI line isolator module is to ensure
that, on a looped addressable system, no short circuit fault
can disable more detection devices then would be lost on a
conventional non-addressable fire circuit.
FC410MIM Mini input module
The FC410MIM mini input module is designed to monitor
fire contacts, such as extinguishing system control,
ventilation control, fire door control etc. The module
provides one identifiable detection spur which is capable
of monitoring multiple normally open contacts or a single
normally closed contact. The FC410MIM may be mounted
in any electrical enclosure with sufficient depth to
accommodate FC410MIM and the contacts monitored by
the IN+ and IN- terminals, i.e., no field wiring. The remote
LED (if required, not supplied) must be located within the
same electrical enclosure.
FC410MIO Small addressable multi I/0
module
The FC410MIO multi I/O module has three class B inputs
and two outputs from latching relays. The class B inputs can
monitor fire contacts such as extinguishing system control,
ventilation control, and fire door control. The two relays
outputs are dry form C that provide volt-free relay
changeover contacts. A maximum of two HVR800 high
voltage relay modules can be individually driven and
controlled by an FC410MIO if all HVR800s are powered by
24VDC or 24VAC. In this application, the HVR800s are
controlled by the two latching relays on the FC410MIO. A
maximum of four HVR800 high voltage relay modules can
be individually driven and controlled by an FC410MIO if all
HVR800s are powered by 120 VAC or 240 VAC. In this
application, the HVR800s are controlled by the four control
outputs (O1+/O1- to O4+/O4-) on the FC410MIO.
FC410SIO Single input and output module
The FC410SIO single input and output module is
designed to provide a monitored open collector input and
a volt free relay changeover output.
FC410SIO can switch up to 2 A @ 24 VDC.
FC420CP Addressable break glass
callpoint (indoor)
The FC420CP addressable break glass callpoint is
designed to monitor and signal the condition of a switch
contact that is operated by activating the break glass
element. The type of alarm generated by the callpoint is
configured in the FireClass FC500
(FC501_FC503_FC506) Console. The FC420CP call
point meets the requirements of EN54 Pt.11. The
FC420CP is fitted to a standard surface mount plastic
back box, standard single gang metal plaster box (35 mm
for flush mounting) or standard single gang metal plaster
box (25 mm) with back box.
FC421CP Addressable break glass
callpoint (outdoor)
The FC421CP weatherproof addressable break glass
callpoint is designed to monitor and signal the condition
of a switch contact that is operated by activating the
break glass element. The type of alarm generated by the
callpoint is configured in the FireClass FC500
(FC501_FC503_FC506) Console. The FC421CP
callpoint meets the requirements of EN54 Pt.11. The
FC421CP is fitted into a standard weatherproof break
glass callpoint housing.
FC430SAB/SAM Sounder base
address modules
The FC430SAM and FC430SAB sounder base address
modules are designed to control a loop powered sounder
base for use with the FC system. The FC430SAB variant
has an integral beacon. They may also be used to drive a
relay base. The units are used to supply the address
decoding in place of a detector, thus providing a loop
powered sounder when used in conjunction with an
FC430SB. The modules are colour matched to the
sounder bases. The FC430SAM and FC430SAB are
locked into the base using the locking device integral to the
sounder base.
FC430SB Loop low power sounder
base
The FC430SB loop low power sounder base provides an
additional sounder function on the FC addressable loop
circuit. The FC430SB loop low sounder base requires an
associated detector in order to operate, as it uses the
address of the detector that is fitted to it. Removal of the
detector or loss of power to the loop will cause the
sounder to cease operating. A maximum of 30 sounder
bases at full volume may be connected to the loop.
4B-I Isolator base
The FC460 and FC400 series detectors, as supplied, use
a common 4B-I isolator base assembly. The base may
be fixed directly to:
British (fixing centers 50 mm) or European (fixing
centers 70 mm) conduit box
FC450EMB European mounting box