7
Table 2: Description of faults
Message
Problem
Mains fault
The control panel is not powered from the mains
Battery
The control panel’s batteries charger not working properly
Low battery
The control panel batteries are empty
Earth
Leakage to earth
24A Output
Shorted 24A Output
24R Output
Shorted 24R Output
Firmware main contr.
Checksum fault
Not programmed dev
Loop device without address
Loop return open
Loop negative signal open
Loop signal open
Loop positive signal open
Loop local short
Local short on loop controller
Loop right short
Right side loop short
Loop left short
Left side loop short
Non answer
Loop device does not answer
Dirty level
Smoke detector only; the dirty threshold has been exceeded
Short circuit
Short circuit on input module
Open circuit
Open circuit on input module
Power supply
Main fault
Wrong value
A loop device has an incorrect value
Stuck output
An output module relay is not switched
Same address
Several loop devices have the same address
Wrong Type
Different loop device from that programmed in the panel
IP Communicator
Communication lost with IP controller
IP receiver
Communication lost with IP receiver
PSTN communicator
The communication with PSTN controller is lost
Telephone line
Telephone line fault
LOG Full
LOG fault
PSTN Action not Ack.
A PSTN action not acknowledged
SC X short
SC x= (1 or 2) short circuit
SC X open
SC x (1 or 2) open terminal
Prog.data main cont
Data programming checksum fault
Prog.data tel.board
Aux Controller data programming checksum fault
Loop Communication
Communication loop fault controller
Display communication
Communication fault on display controller
LOOP x NOISY
The devices on the loop x (1, 2 or 3) do not communicate
properly with the panel. Check the quality of wiring.
REPEATER COMMUNIC.
A repeater on the RS485 does not respond
MFI x COMMUNIC.
(x from 1 to 4)
67PRINTER x FAULT
(x from 1 to 4)
PRINTER x ABSENT
(x from 1 to 4)
MFI x SERIAL CHANN.
(x from 1 to 4)
MFI x INy SHORT
(x from 1 to 4; y from 1 to 5)
DEFAULT DATA
The fire panel resets to default data