MANUAL for the basic control panel | CCB2.0
31
Mapping for MODBUS communication protocols:
Write: The following table shows the write function of each communication address:
Address
Description
Writing
1010
Write position disconnector switch I1
0Off, 1Manual, 2Auto (Subject
to interlocking function in J21)
1064
Write signal configuration empty
0Never, 1Standard, 2
Conductivity control
1066
Write pre-set on configuration
0Disabled 1Enabled
1068
Write pre-set on cycle configuration
Write range 0-10 cycles
1070
Write Language
0Spanish 1English 2German
3French
Address
Description
Writing range (increase)
Factory setting
1012
Write conductivity Set-Point
0-1999µS/cm*(increase
1µS/cm)
300 µS/cm
1030
Write Timer T01
30-1000s*(increase 15s)
90s
1032
Write Timer T02
1-15 min*(increase 1min)
5min
1034
Write Timer T03
1-60 min*(increase 1min)
10min
1036
Write Timer T04
30-400min*(increase 30min)
60min
1038
Write Timer T05
0-24h*(increase 1h)
0min=never
1040
Write Timer T06
0-24h*(increase 1h)
1h
1042
Write Timer T07
5-360s*(increase 5s)
30s
1044
Write Timer T08
10-60min*(increase 5min)
15min
*These values must be entered in seconds in the write for such addresses