MANUAL for the basic control panel | CCB2.0
35
Object
Description
Writing range (increase)
Factory
setting
SETPOINT µS*
(Analog_Output:9)=1012
Write conductivity
Set-Point
0-1999µS/cm*(increase
1µS/cm)
300 µS/cm
SET Timer 1*
(Analog_Output:1)=1030
Write Timer T01
30-1000s(increase 15s)
90s
SET Timer 2*
(Analog_Output:2)=1032
Write Timer T02
1-15 min(increase 1min)
5min
SET Timer 3*
(Analog_Output:3)=1034
Write Timer T03
1-60 min(increase 1min)
10min
SET Timer 4*
(Analog_Output:4)=1036
Write Timer T04
30-400min*(increase
30min)
60min
SET Timer 5*
(Analog_Output:5)=1038
Write Timer T05
0-24h(increase 1h)
0min=never
SET Timer 6*
(Analog_Output:6)=1040
Write Timer T06
0-24h(increase 1h)
1h
SET Timer 7*
(Analog_Output:7)=1042
Write Timer T07
5-360s(increase 5s)
30s
SET Timer 8*
(Analog_Output:8)=1044
Write Timer T08
10-60min*(increase 5min)
15min
* These objects are bidirectional: In addition to working as writing, they show the reading of their
states.
Read: The following table shows the read function of each communication objects:
Object
Description
Reading
PROBE GET µS
(Analog_Input:0)=2012
Read conductivity value
0-1999 µS/cm*
PROBE GET TEMP
(Analog_Input:1)= 2014
Read temperature value ºC
Ej. 18 18,15ºC