6600 – 6665 – 6700 – 6765
E
N
G
L
I
S
H
13
5 - BASIC PROGRAMMING MODE
6600 / 6665
This level includes the functioning parameters of the softener related to the site conditions.
ENTERING BASIC PROGRAMMING MODE
A- The valve is in service position. Press the button for 5 seconds. The program arrow turns on and the
first display viewed is used to set the inlet water hardness.
B- The
and set buttons are used to set the parameter values of different displays.
C- Passing to the next display, push the
button.
Note: depending on the current programming, certain displays will not be viewed or set.
5.1 WATER HARDNESS
Not viewed in timeclock regeneration mode or when the volume override is activated.
The unit of measure used for the parameter is °tH(1). Adjust the value with the and set buttons.
Ex.: Hardness 30 °tH
(1)
[H - - - - 30]
5.2 WATER HARDNESS AFTER THE MIxING VALVE (P)
Not viewed in timeclock regeneration mode, with the volume override activated, or in US format, or if 8 set
on 1
(2)
.
Press button. The letter “P” identifies this parameter. The unit of measure is the °tH(1). Adjust the value
with the
and set buttons.
Ex.: Hardness after the mixing valve 6 °tH
(1)
: [P - - - - 6]
5.3 REGENERATION TIME
Not viewed in meter immediate regeneration mode.
Press the button. Set the regeneration time with the and set buttons.
Ex.: Regeneration at 2:00 A.M. [--2:00--]
ExITING BASIC PROGRAMMING MODE
Press once again the button. the electronics returns in service.
(1) The unit of measure depends on the display format chosen.
All examples above are based on the cubic meter format -see point 6.17.
(2) See point 6.24