EasyManua.ls Logo

Flomec RT40 - Electrical Installation; Terminal Identification

Flomec RT40
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
4. Electrical Installation
All wiring connections should be made with good quality shielded instrument cable; wiring
between terminals which are inside the instrument enclosure, or between a flowmeter and an
integrally mounted instrument may use non-shielded wire. Cable shields or drain wires should
be connected to the instrument ground (GND) at the instrument end only isolate the
shield/drain wire at the flowmeter end of the cable.
The terminal connections on the instrument will allow for usage of wiring up to 1.5mm
2
cross
section (16AWG). Wire insulation should be stripped to a length of 7mm and conductors
should be fitted to the terminals so that there is minimal exposed conductor. Terminals can be
tightened with a 2.5mm flat blade screw driver.
4.1 Terminal Identification
The terminal connections are divided into 4 separate sections by their function, see image
below. There is a separate ground (GND) terminal in each section of terminals; as this
instrument has a common ground, all GND terminals are internally connected.

Related product manuals