EP5 Electro Pneumatic Digital Positioner FCD PMENIM0006-00-A5 12/18
23
Note: All PMV-Positioners are serialized. Please
note down, and provide the serial number when
contacting the factory for trouble shooting or
service.
Signal change has no effect on the actuator
position.
Check indicator and screw.
Check air supply to positioner and tubing to
the actuator.
Check input signal to positioner.
Check diaphragm for damage or leakage.
Check pilot valve function.
Check cam for correct setting.
Check I/P output
Signal change results in actuator running to end
positions.
Check coupling between positioner and
actuator.
Check cam position and locking screw.
Check input signal.
Inaccurate positioning.
Dirty or worn pilot valve.
Defective or leaking diaphragm.
Input signal fluctuates.
Incorrect sizing of actuator.
Valve/actuator ”stiction”.
High valve/actuator breakaway torque.
Loose cam.