1535/1537
Users Manual
20
Any of the following conditions will stop an insulation test:
User stops the test (push D)
Time limit is complete (1537 only)
Interference on the test circuit
Breakdown occurs with ramp test enabled (1537 only)
DAR / PI / DD reaches time limit
Battery is depleted
When the insulation test is done, the Tester beeps if a potentially
hazardous voltage remains on the test terminals due to charged-circuit
capacitance or from the presence of an external voltage.
4. When the test is done, the Tester shows a prompt to store the results. If
appropriate, store the test results (see next section). Otherwise, push
G
to bypass the prompt. The results are not stored.
Store Test Results (1537 only)
When the insulation test is done, the Tester shows a prompt to save the
results. The Tester memory stores the results of up to 99 insulation tests.
Table 6. Insulation Resistance Measurements
Item Description
A
Digital main display
B
Bar graph