1535/1537
Users Manual
28
General Specifications
For a list of specifications for 1535/1537, please refer to the 1535/1537
Insulation Tester Quick Reference Guide, PN 5304200.
Electrical Specifications
The Tester’s accuracy is specified for 1 year after calibration at operating
temperatures of 10 °C to 30 °C. For operating temperatures outside the range
(-10 °C to +10 °C and +30 °C to +50 °C), add ±0.25 % per °C for 5 % bands and
add ±1 % per °C for 20 % bands.
Tab l e 1 0 . Accesso ries
Accessory Part No.
10 kV Clamp (Red/Black/Green) 4103525
Table 11. Number of Insulation Resistance Measurements
Un (V)
R
load
(Ω)
Number of
Measurements
250 V 250 kΩ 6500
500 V 500 kΩ 3800
1000 V 1 MΩ 2200
2500 V 2.5 MΩ 1300
Table 12. Insulation Resistance Measurement
Test Voltage Range Resolution Accuracy
250 V
<200 kΩ unspecified unspecified
200 kΩ to 500 kΩ 1 kΩ 5 %
0.50 MΩ to 5.00 MΩ 10 kΩ 5 %
5.0 MΩ to 50.0 MΩ 100 kΩ 5 %
50 MΩ to 500 MΩ 1 MΩ 5 %
0.50 GΩ to 5.00 GΩ 10 MΩ 5 %
5.0 GΩ to 50.0 GΩ 500 MΩ 20 %
>50 GΩ unspecified unspecified