13
Insulation Tester
Insulation Test Settings
Dielectric Absorption Ratio
If appropriate, as part of the insulation test, the Tester stores the dielectric
absorption ratio (DAR) with the measurement. A DAR test has a 1-minute duration
and is measured and stored as invalid data for all insulation tests <1 minute. The
DAR test automatically stops when the insulation test time reaches 1 minute. The
results are available for display after test or by storing the test results and viewing
the DAR eld in record. See
Figure 6
.
The eld is identied by:
s
R
R
DAR
30
min1
s
R
R
DAR
15
min1
[CN]
The Tester also does the DAR test in accordance with the Chinese standards:
s
R
R
DAR
30
min1
s
R
R
DAR
15
min1
[CN]
Note
If appropriate, as part of the insulation test, the Tester stores the
capacitance measurement. The results are available for display after the
test is complete by viewing the capacitance eld in the stored record.
Figure 6. Dialectric Absorption Ratio
1 min.
1
1x = DAR
30 sec
1 min
R
R
DAR =
2