Before an Insulation Test
Note
The Tester does not have specied accuracy below 200 kΩ . When you
do a test below 200 kΩ or with the leads shorted, the Tester can show a
reading. This is normal for the input circuitry conguration for this Tester.
Only the readings within the specied accuracy range are accurate.
Before an Insulation Test
The Tester includes features that let you adapt the test to your requirements.
You can:
Dene a test voltage
Measure polarization index (PI)
Measure dielectric absorption ratio (DAR)
1537/1537-II only:
Make a ramp test selection
Measure dielectric discharge (DD)
Compare insulation resistance
Set a time limit/duration for the test
Use these features alone or in combination. Congure or validate (as appropriate)
each feature before you start an insulation test. For connections, see
Figure 7
.
Figure 7. Insulation Test Connections