Earth Ground Clamp
Safety Information
3
Do not use the Product above its rated
frequency.
Limit operation to the specified measurement
category, voltage, or amperage ratings.
Do not touch voltages >30 V ac rms, 42 V ac
peak, or 60 V dc.
Hold the Product behind the tactile barrier.
The battery door must be closed and locked
before you operate the Product.
Replace the batteries when the low battery
indicator shows to prevent incorrect
measurements.
Remove the batteries if the Product is not used
for an extended period of time, or if stored in
temperatures above 50 °C. If the batteries are
not removed, battery leakage can damage the
Product.
Do not operate the Product with covers
removed or the case open. Hazardous voltage
exposure is possible.
Repair the Product before use if the battery
leaks.
Use only specified replacement parts.
Have an approved technician repair the
Product.
Remove the input signals before you clean the
Product.
Do not operate within external low frequency
magnetic fields >30A/m.
Symbols used on the Product and in this manual are
explained in Table 1.

Other manuals for Fluke 1630-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fluke 1630-2 and is the answer not in the manual?

Fluke 1630-2 Specifications

General IconGeneral
TypeEarth Ground Clamp Meter
Ground Resistance Range0.025 Ω to 1500 Ω
DisplayLCD
Data LoggingYes
Operating Temperature-10 °C to 50 °C
Storage Temperature-20 °C to 60 °C
Ground Resistance Accuracy±(1.5% + 0.02 Ω)
Jaw Opening32 mm
Power SupplyAA batteries
Safety RatingCAT IV 600 V