EasyManuals Logo

Fluke 1738 User Manual

Fluke 1738
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
Power Logger
Function Selection Buttons
21
Study Type
Depending on the application, select either Load Study or
Energy Study.
Energy Study: Select this study type when voltage
measurements for a power quality assessment and
power and energy values that include active power
(W) and PF are required.
Load Study: For convenience, some applications
require you to measure only the current that makes the
connection to the point to measure.
Typical applications are:
- Verify the circuit capacity before adding additional
load.
- Identify situations where the allowable load can be
exceeded.
Optionally, a nominal voltage can be configured to get
pseudo-apparent power readings.
Power Quality
Select the power quality standard (available on 1738 or
1736 with 1736/Upgrade or IEEE 519/Report license) for
compliance evaluation.
EN 50160: voltage characteristics of electricity
supplied by public distribution networks.
The Logger supports these parameters:
Frequency
Voltage Variations
Voltage Harmonics and Voltage THD
Unbalance
Events
IEEE 519: recommended practice and requirements for
harmonic control in electric power systems.
The standard defines limits for voltage harmonics, voltage
THD, current harmonics and TDD (total demand
distortion). The limits for current harmonics and TDD
depend on the ratio of maximum demand load current I
L
to
the short circuit current I
SC
. Set the values with and
.
Note
If the values of
I
SC
and
I
L
are not currently
available, you can update these values at a later
time with the Energy Analyze Plus software.
Set the Harmonics Standard to off when the harmonics
compliance evaluation is not required.

Table of Contents

Other manuals for Fluke 1738

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fluke 1738 and is the answer not in the manual?

Fluke 1738 Specifications

General IconGeneral
Product typeThree phase power measurement logger
Cable lock slot typeKensington
International Protection (IP) codeIP50
Operating altitude0 - 4000 m
Non-operating altitude0 - 12000 m
Storage temperature (T-T)-20 - 60 °C
Operating temperature (T-T)-10 - 50 °C
Operating relative humidity (H-H)10 - 95 %
Built-in displayYes
Display diagonal4.3 \
Touchscreen typeResistive
Display resolution480 x 272 pixels
Display technologyTFT
Efficiency68.2 %
Battery life4 h
Charging time6 h
Battery voltage3.7 V
Input frequency50/60 Hz
Battery capacity9.25 Wh
Power consumption (max)50 VA
Battery life (power save mode)5.5 h
Weight and Dimensions IconWeight and Dimensions
Depth55 mm
Width198 mm
Height167 mm
Weight1100 g
Power adapter weight400 g
Power supply dimensions (WxDxH)130 x 45 x 130 mm