EasyManua.ls Logo

Fluke 6500 - Specifications; General Specifications

Fluke 6500
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Users Manual
Specifications
35
Specifications
General Specifications
Size .................... 200 mm (L) x 275 mm (W) x 100 mm (H)
Weight ....................................................................... 3.0 kg
Power Supply ............... 240 V + 10 % - 15 %, 50 Hz ± 2 %
Power Consumption (Tester) ................ 13 W typical (idle)
....................................... 60 W max. during 25A Bond Test
Operating temperature ......................................0 to +40 °C
Storage temperature ......................................-10 to +60 °C
Relative Humidity
............................................ non condensing < +10 °C
.............................................. 95% from +10 to +30 °C
.............................................. 75% from +30 to +40 °C
Operating Altitude........................................0 up to 2000 m
Sealing ..................... IP-40 (enclosure), IP-20 (connectors)
EMC ........................... complies with EN61326-1, criteria B
EMI Immunity ............................................................ 3 V/m
Safety ............... Complies with IEC/EN61010 -1 2
nd
edition
DIN VDE0404-1 and DIN VDE0404-2
IEC/EN 61557, part 1,2,4
CAT II, 300 V, pol 2
Printer – PC RS232 Interface
Baud rate .................................... factory default 9600,
selectable 1200, 2400, 9600, 19200, 38400
Data bits .....................................................................8
Stop bits .....................................................................1
Parity........................................................................no