3. Measure the resistance by touching the probes to the desired
test points of the circuit.
4.
Read the measured resistance on the display.
Note
If the resistance is <30
e
, the continuity beeper sounds
and indicates a short circuit.
Measure Microamps
μ
A
The μA dc () function on the Product is primarily for HVAC flame
rod testing.
To test a heating system flame rod (see Figure 2):
1.
Turn the heating
unit off.
2.
Locate the wire between the gas-burner controller a
nd the
flame rod, and b
r
eak this connection.
3.
Turn the rotary switch to
.
4. Use alligator clips to connect test leads between th
e flame
sensor probe an
d control-module wire.
5.
Turn he
ating unit on.
6.
Read the measured amps on the display.
7.
Refer to the heating unit documentation for what the
desired
value should be.