Use the Product
Make Measurements 3
3-17
Measure Voltage with TL175
With the TL175 test lead, the Product can measure Discharge Volts, VDC, VAC, and
Ripple Volts.
To measure voltage:
1. Connect TL175 to the BTL_A adapter.
2. Connect the BTL_A adapter to the Product.
3. Turn the rotary switch to the necessary position.
For details about the measurements, refer to the “Measure Discharge Volts”, “Measure
DC Voltage”, “Measure AC Voltage” and “Measure Ripple Voltage” sections.
As an example, Figure 3-5 shows how to measure dc voltage with the TL175 test lead.
UPS
TL175
Guard
drops
hsn053.eps
Figure 3-5. Measure DC Voltage with TL175