No. Menu name Specification Description
2_1 Start level 1 ft WritableCentral System TextStart
level 1 (ft)
Start level for first pump.
2_2 Stop level 1 ft WritableCentral System TextStop
level 1 (ft)
Stop level for first pump.
2_3 Start level 2 ft WritableCentral System TextStart
level 2 (ft)
Start level for second pump.
2_4 Stop level 2 ft WritableCentral System TextStop
level 2 (ft)
Stop level for second pump.
2_5 Start level 3ft WritableCentral System TextStart
level 3 (ft)
Start level for third pump.
2_6 Stop level 3 ft WritableCentral System TextStop
level 3 (ft)
Stop level for third pump.
2_7 Start level 4 ft WritableCentral System TextStart
level 4 (ft)
Start level for fourth pump.
2_8 Stop level 4 ft WritableCentral System TextStop
level 4 (ft)
Stop level for fourth pump.
2_9 High level ft WritableCentral System TextHigh
level (ft)
High level alarm limit.
2_10 Low level ft WritableCentral System TextLow
level (ft)
Low level alarm limit.0 - disables the function
2_11 Random start range ft WritableCentral System
TextRandom start range (ft)
Random start range
2_12 Sensor range ft WritableCentral System TextSensor
range (ft)
Sensor range.
2_13 Sensor calibration ft WritableCentral System TextSensor
calibration (ft)
Sensor calibration offset.
3 P1 current A Read only Measured current for first pump.
3_1 P1 high current A WritableCentral System TextP1 high
current (A)
High current alarm limit for first pump.
3_2 P1 low current A WritableCentral System TextP1 low
current (A)
Low current alarm limit for first pump.
3_3 P1/P3 Current range
A
Writable Current transformer range for pump 1
3_4 Current factor P1/P3 Writable Current factor for P1 versus P3. Used when P1 and P3 are difference
sizes. Default is 1.0
4 P2 Current A Read only Measured current for second pump.
4_1 P2 high current A WritableCentral System TextP2 high
current (A)
High current alarm limit for second pump.
4_2 P2 low current A WritableCentral System TextP2 low
current (A)
Low current alarm limit for second pump.
4_3 Current range P2/P4
A
Writable Current transformer range for pump 2 and 4