Read Operational Data
Read Operational Data
Available Functions
Functions that may be available are described below. Whether a function is available or
not, depends on previous installation and configuration.
Menus to use
Menu name No. Description Comment Value
can be
reset?
Level 2_ Sump level No
P1 current – P4 current 3_– 6_ Current for Pump 1–4. No
P1 start counter 7_1 Total number of starts for
pump 1.
Yes
P1 run hour 7_2 Total runtime for pump 1. Yes
.. ..
P4 run hour 7_8 Total runtime for pump 4. Yes
Overflow flow 8_16 Estimated overflow flow. No
Overflow volume 8_17 Estimated overflow
volume.
Yes
Overflow count 8_18 Number of overflows Yes
No. of major overfl. 8_19 Number of major
overflows
An overflow is also a major overflow
when no other overflow has
occurred for the last 24 hours.
Yes
Overflow time 8_20 Total overflow time Yes
Rain 9_ Daily rain value No
Free flow 10_1 Estimated free flow. The free flow is also called the
inflow, and is the flow into the
sump.
No
Pumped volume 10_2 Estimated volume
pumped away from sump.
Yes
Sump volume 10_3 Estimated volume
remaining in sump.
Yes
Calc. capacity P1 – P4 12_1 –
12_4
Capacity for Pump 1–4. No
Reset operational data
1. View the relevant operation menu.
Example: P1 start counter menu.
2. Press OK.
Result: Menu window shows "Reset value? No".