Program Program
Code Function Code Description Entry Code
14 AB06030 Rev. 0.6 5/96
300
System Volume Accuracy Directory
300
301 Transaction Control Enter: "0" Local Tray Switch 301
"1" Print Key
"2" Remote
"3" Master Reset __
302 Maximum Preset Enter: Five (5) digits in whole units 302
Volume (e.g., up to 99,999 units)
"00000" disables option __ __ __ __ __
303 Minimum Preset Enter: Five (5) digits in whole units 303
Volume (e.g., up to 99,999 units)
"00000" disables option __ __ __ __ __
304 Auto Preset Enter: Five (5) digits in whole units 304
(e.g., 99,999 units)
"00000" disables option __ __ __ __ __
305 Auto Preset Increment Enter: Four (4) digits in whole units 305
to increment the auto preset.
(e.g., 0100 units)
"0000" disables option __ __ __ __
306 Blank Downcounter Enter: "0" Downcounter to be Displayed 306
"1" No Downcounter Displayed __
307 Volumes for Local Enter: Five (5) digit number indicating 307
Storage the volumes that will be stored in
local storage.
Note:
A maximum of three (3) volumes will be stored.
1st digit - Raw Volumes (RW)
2nd digit - Gross Volumes (GR)
3rd digit - Gross at Standard Temperature
Volumes (GT)
4th digit - Net Volumes (NT)
5th digit - Mass Totals (MA)
A zero (0) in the digit indicates that
the volume will not be saved in local
storage, a (1) indicates the volume
will be saved in local storage. __ __ __ __ __
308-339 Unassigned at Present 308-339
340 Protection of Program Enter: "0" for Weights and Measures Mode 340
Codes 380-389 "1" for Program Mode __