Program Program
Code Function Code Description Entry Code
4 AB06030 Rev. 0.6 5/96
008 D/C Output Relay 1 Enter: "00" No Assignment (NAS) 008
W/O Quad OPV "01" Pulse Output (POT)
Terminals 9 & 10 "02" Additive Relay 1 (ADD1)
(Position #1) "03" Additive Relay 2 (ADD2)
Terminals 57 & 58 "04" Additive Relay 3 (ADD3)
(Position #2) "05" Additive Relay 4 (ADD4)
"06" Additive Relay 5 (ADD5)
W/Quad OPV "07" Additive Relay 6 (ADD6)
Terminals 11 & 10 "08" Additive Relay 7 (ADD7)
(Position #1) "09" Block Valve Relay 1 (BVR1)
Terminals 15 & 14 "10" Block Valve Relay 2 (BVR2)
(Position #2) "11" Block Valve Relay 3 (BVR3)
"12" Block Valve Relay 4 (BVR4) __ __
Note: When using a Smart Additive Subsystem, options 02 through 08 (Additive Relays) are not available for selection.
009 D/C Output Relay 2 Enter: "00" No Assignment (NAS) 009
W/Quad OPV "01" Pulse Output (POT)
Terminals 13 & 12 "02" Additive Relay 1 (ADD1)
(Position #1) "03" Additive Relay 2 (ADD2)
Terminals 17 & 16 "04" Additive Relay 3 (ADD3)
(Position #2) "05" Additive Relay 4 (ADD4)
"06" Additive Relay 5 (ADD5)
"07" Additive Relay 6 (ADD6)
"08" Additive Relay 7 (ADD7)
"09" Block Valve Relay 1 (BVR1)
"10" Block Valve Relay 2 (BVR2)
"11" Block Valve Relay 3 (BVR3)
"12" Block Valve Relay 4 (BVR4) __ __
Note: 1. This code is only available for use if the Quad OPV option has been purchased with the AccuLoad II. The terminals listed for this
code are located on the Quad OPV board.
2. When using a Smart Additive Subsystem, options 02 through 08 (Additive Relays) are not available for selection.
010 A/C Input 1 Enter: "00" No Assignment (NAS) 010
Terminals 98 & 101 "01" Additive Feedback 1 (AFB1)
(Position #1) "02" Additive Feedback 2 (AFB2)
Terminals 106 & 109 "03" Additive Feedback 3 (AFB3)
(Position #2) "04" Additive Feedback 4 (AFB4)
"05" Additive Feedback 5 (AFB5)
"06" Additive Feedback 6 (AFB6)
"07" Additive Feedback 7 (AFB7)
"08" Block Valve Feedback 1 (BVF1)
"09" Block Valve Feedback 2 (BVF2)
"10" Block Valve Feedback 3 (BVF3)
"11" Block Valve Feedback 4 (BVF4)
"12" First/Second High Flow (FSC)
"13" Printer Tray Switch (PTS) *
"14" Permissive 1 Contact (PRC1)
"15" Permissive 2 Contact (PRC2)
"16" Valve Power (VPW)
"17" Valve Stem (VST) __ __
Note: 1. Or can be used for Master Reset.*
2. When using a Smart Additive Subsystem, options 01 through 07 (Additive Feedbacks) are not available for selection.