To move to the next horizontal parameter press the button
:
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button
:
Simultaneity
Max pumps nr.X
Turn-Off MANUAL
0=ON XXXsec
Rotating pumps
0=NO 1=R 2=A X
Simultaneity
Max pumps nr.X
The parameter “Simultaneity Max pumps” will set the number of pumps can be used
simultaneously. For example, setting the value to “1” it will have a maximum of 1 pump even if
the conditions for both pumps are active.
The “X” indicates the setting of the parameter to modify.
The range of value is from 1 to 2.
Factory default setting: 2 (FULL-APP²).
Rotating pumps
0=NO 1=R 2=A X
Simultaneity
Max pumps nr.X
Change pump
Every XXX hours
Rotating pumps
0=NO 1=R 2=A X
With the parameter “Rotating pumps” is possible to activate/select the mode in which the
pumps will alternately start.
- 0=NO: setting “0” there will be no rotation of starting pumps. The pumps will start and stop
depending on their own settings of activation and deactivation.
Note: the condition for starting pump2 will also start pump 1.
- 1=R: setting “1” the rotation is activated with the following logic:
At every activation of the first starting condition the pumps will start in a cyclic order; at every
activation of the second condition will result in the start of the second pump. The stopping of
the pumps will be by in reverse order, firstly stopping the pump that started last, and then
stopping the pump that started first.
- 2=A: setting “2” the rotation will happen based on the number of starts of each pump
(displayed under the operating parameter “St XXX”) to balance the number of starts between
the pumps. The stopping of the pumps will order the pump with the least number of starts (in
order to have it re-start next and increase the number of restarts to try to balance it).
- Setting “3” the rotation of the pumps will be based on the number of working hours of each
pump (displayed under the operating parameter “h XXX”) in order to balance the load and
number of working hours between the pumps. The stopping of the pumps will be in order of the
most working hours.
- Setting “4” will activate the timer rotation: the rotation between pumps will be based on the
programmable timer described in the next parameter (“Change Pump every XXX hour”).
- Setting “5” the rotation will have the following logic:
At every activation of the first starting condition will result in a cyclic order of the pumps; at
every activation of the second condition will result in the start of the second pump. The
stopping of the pumps will be in sequence in which the pumps started. Firstly stopping the
pump which started first and then stopping the pump that started last.
The “X” indicates the setting of the parameter to modify.
The range of value is from 1 to 5.
Factory default setting: 1.
Change pump
Every XXX hours
Rotating pumps
0=NO 1=R 2=A X
Restart Setting
Restart1 XXX min
NOTE: in the case the pump intended to start doesn’t activate (whatever the reason), the other pump will
be activated automatically (in the case is set to the parameter "Simultaneity Max pumps" to 2).
NOTE: If there is a need to manage the pumps separately is recommended to switch the program
operating to MULTITANK