36
To move to the next horizontal parameter press the button
:
It is possible to activate the sound alarm output (and also all the other alarm outputs described later) for 15 types of
alarms. One or more alarms can be activated as desired. To activate an alarm set the value from “0” to “1” in the
following table
For example, the mask “100110000000000” will activate the following alarms: V Min, V Max, Min Level e Max Level.
The FULL-APP² always shows to display each alarm detected, but it will activate the alarm output only if it’s configured
properly.
N.B.: The alarms “I Min, cos ø Min”, “I max”, ”Service Request”, “Max Starts per Minute/Hour”, “Intervention
Klixon”, “Water in Oil Chamber” e “Max Continuous Operation”, TO BE ACTIVATED, MUST BE ASSOCIATED TO
AT LEAST ONE PUMP; THERE MUST BE ACTIVE AT LEAST ONE OF THE “ALARMS PUMP”.
Configuration
XXXXXXXXXXXXXXX
Mode
0=NO 1=SI 2=P X
Configuration
XXXXXXXXXXXXXXX
The parameter “Configuration” sound alarm output is possible to set which alarms will activate
the output (with mode described in the previous parameter).
The “X” indicates the setting of the parameter to modify.
Factory default setting: 100111111100110.
NOTE: the alarms in gray are automatically sent only if is mounted GSM modem.
There is no need any configuration and it's not possible to disable these features.
1
not be disabled
111
0
(only whit GSM modem) Absence/Return mains
(only whit GSM modem) Black-out Max level
(only whit GSM modem) Low battery
11
0000
Max start per minute, Max start per hour
Max Klixon interventions
Detection of water in oil chamber
Max continous working
11
00
V Min, V Max
Phase Seq., Min Hz, Max Hz
4-20 mA device malfunction
Min level
00000
1111111
0
1
0
1
0
1
I max
Service
Max level
Pump 1 alarms
Pump 2 alarms
Pump 3 alarms
I Min, cosφ
Min
ALARM ON
ALARM O FF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18