2.8 Safety devices
2.2
SW
2.2 BOILER OFF
(switches off the boiler to prevent overheating)
Tap “Boiler off"
Automatic mode is switched off
Control system follows the boiler shutdown procedure
Pumps continue to run
3 MAIN SWITCH
(switches off the power supply)
Before carrying out work on/in the boiler:
Tap “Boiler OFF”
Automatic mode is switched off
Control system follows the boiler shutdown procedure
Switch off the main switch and let the boiler cool down
4 HIGH-LIMIT THERMOSTAT (STL)
(protection against overheating)
The STL switches off the combustion system when the boiler reaches 105°C. The
pumps continue to run. Once the temperature falls below approx. 75°C, the STL can
be reset mechanically.
SV SAFETY VALVE
(protection against overheating/excess pressure)
When the boiler pressure reaches a maximum of 3 bar, the safety valve opens and the
heated water is blown off in the form of steam.
Safety
2
Safety devices
Operating Instructions P4 Pellet | B0870417_en 17