WARNING
Incorrect inspection and cleaning:
Incorrect or insufficient inspection and cleaning of the boiler can cause serious
faults in combustion (e.g. spontaneous combustion of carbonisation gases / flash
fires) and this can lead to serious accidents and damage!
Take the following precautions:
❒ Clean the boiler following the instructions in the instruction manual. Follow the
boiler operating instructions.
NOTICE
We recommend that you keep a maintenance book in accordance with ÖNORM
M7510 of the Technical Directive for Fire Prevention (TRVB)
4.2 Inspection and cleaning
❒ Regular cleaning of the boiler extends its life and is a basic requirement for
smooth running.
❒
Recommendation: use an ash vacuum for cleaning.
4.2.1 Inspection
Checking the system pressure
❒ Check the system pressure on the pressure gauge
➥ The value must be 20% above the pre-stressed pressure of the expansion tank
NOTICE! Check that the position of the pressure gauge and rated pressure of
the expansion tank match your installer's specifications!
If the system pressure decreases:
❒ Top up with water
NOTICE! If this happens frequently, the seal of the heating system is faulty! Inform
your installer
If large pressure fluctuations are observed:
❒ Ask an expert to inspect the expansion tank
Checking the safety valve
❒ Check the seal of the safety valve regularly and ensure that the valve is not dirty
NOTICE! Inspection work must be carried out in accordance with the
manufacturer’s instructions.
4
Boiler Servicing
Inspection and cleaning
26 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com