2.8 Safety devices
3 MAIN SWITCH
(switches off the power supply)
Before carrying out work on the boiler:
Tap “Boiler off”
Automatic mode is switched off
Control system follows the boiler shutdown procedure
Switch off the main switch and let the boiler cool down
4.5 BOILER OFF
(switches off the boiler to prevent overheating)
Tap “Boiler off”
Automatic mode is switched off
Control system follows the boiler shutdown procedure
The pumps continue to run
NOTICE! Never use the main switch!
8 HIGH-LIMIT THERMOSTAT (STL)
(protection against overheating)
The STL switches off the combustion system when the boiler reaches 105°C. The
pumps continue to run. Once the temperature falls below approx. 75°C, the STL can
be reset mechanically.
TV THERMAL DISCHARGE VALVE
(protection against overheating)
The thermal discharge valve opens at approx. 100°C and feeds cold water to the
safety heat exchanger to lower the boiler temperature
SV SAFETY VALVE
(protection against overheating/excess pressure - supplied by the
customer)
When the boiler pressure reaches a maximum of 3 bar, the safety valve opens and the
heated water is blown off in the form of steam.
Safety
2
Safety devices
Operating Instructions TX 200-250 | B1060217_en 19