EasyManua.ls Logo

Froling TX 200 - Emissions measurement by chimney sweep or regulatory body

Froling TX 200
55 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.3 Emissions measurement by chimney sweep or regulatory body
Various legal regulations stipulate that heating systems must be inspected
periodically. In Germany this is regulated by the First Federal Emissions Protection
Ordinance (BimSchV) in the last amended version, and in Austria by various state
laws. The boiler must always be cleaned 2-3 heating days prior to measurement. It is
important to ensure that there is adequate heat consumption on the day of the
measurement. (e.g. storage tank must be able to take heat for the duration of the
measurement).
4.3.1 Measurement at nominal load
For the highest possible heat consumption:
Make sure that heating pumps are switched on
Open mixing valves and radiator valves
Set the DHW tank loading time to the current time
Set the boiler temperature setpoint to 85°C
NOTICE! Chimney-sweep mode takes over this function
Activate chimney-sweep mode
Activate “Chimney-sweep mode” in the quick menu
The chimney sweeper program is started. The system is operated for 45
minutes at nominal load. For this purpose the maximum boiler and heating
circuit flow temperature and DHW tank loading are released.
Permitted measurement parameters:
Flue gas temperature at approx. 140°C
(+/- 20°C depending on the cleanliness of the boiler)
O
2
content of the flue gas between 8 and 12%
(corresponds to a CO
2
content between 13 and 9%)
Boiler temperature above 80°C
4.3.2 Measurement at partial load (if necessary)
For heat consumption:
Make sure that heating pumps are switched on
Open mixing valves and radiator valves
Set the DHW tank loading time to the current time
Force partial load:
After measuring at nominal load, set the boiler temperature setpoint to 3°C below
the actual boiler temperature at nominal load
Permitted measurement parameters:
Flue gas temperature at approx. 120°C
(+/- 20°C depending on the cleanliness of the boiler)
O
2
content of the flue gas between 10 and 14%
(corresponds to a CO
2
content between 7 and 11%)
Boiler temperature above 75°C
4
Boiler Servicing
Emissions measurement by chimney sweep or regulatory body
50 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com

Table of Contents

Related product manuals