129
g
1x2
AC voltage too high
Behavior Grid conditions are thoroughly tested and as soon as they are
again within the permissible range, the inverter will resume
feeding power into the grid.
Remedy Check grid connections and fuses
Should the status code persist, you should contact your system
installer
1x3
AC voltage too low
Behavior Grid conditions are thoroughly tested and as soon as they are
again within the permissible range, the inverter will resume
feeding power into the grid.
Remedy Check grid connections, breakers and disconnect
Should the status code persist, you should contact your system
installer
1x5
AC frequency too high
Behavior Grid conditions are thoroughly tested and as soon as they are
again within the permissible range, the inverter will resume
feeding power into the grid.
Remedy Check grid connections and fuses
Should the status code persist, you should contact your system
installer
1x6
AC frequency too low
Behavior Grid conditions are thoroughly tested and as soon as they are
again within the permissible range, the inverter will resume
feeding power into the grid.
Remedy Check grid connections and fuses
Should the status code persist, you should contact your system
installer
1x7
No AC grid detected
Behavior Grid conditions are thoroughly tested and as soon as they are
again within the permissible range, the inverter will resume
feeding power into the grid.
Remedy Check grid connections and fuses
Should the status code persist, you should contact your system
installer
108
Islanding detected