Class 3 status
codes
Class 3 comprises status codes that may
appear during feed-in operation and that do
not cause a permanent interruption of the
operation of feeding power into the grid.
After automatic disconnection from the grid and waiting for its conditions to return to those
stipulated, your inverter will try to resume feed-in operation.
Behavior Grid conditions are thoroughly tested and as soon as they are
again within the permissible range, the inverter will resume
feeding power into the grid.
Remedy Should the status code persist, you should contact your system
installer
109
General grid error
This error is always displayed first for grid errors. After reviewing all power stage sets, the
grid error is specified in more detail: 1x1 / 1x4 or the display remains at "109" (e.g., when
2 phases report "104" and one phase "101")
Behavior Grid conditions are thoroughly tested and as soon as they are
again within the permissible range, the inverter will resume
feeding power into the grid.
Remedy Check grid connections and fuses
Should the status code persist, you should contact your system
installer
301
Overcurrent (AC)
Description Short interruption of power feeding into the grid due to overcur-
rent.
The inverter returns to the startup phase.
Remedy Fault is rectified automatically
If this status code keeps recurring, contact your system installer
302
Overcurrent (DC)
Description Short interruption of power feeding into the grid due to overcur-
rent.
The inverter returns to the startup phase.
Remedy Fault is rectified automatically
If this status code keeps recurring, contact your system installer
303
Over-temperature buck converter