EasyManua.ls Logo

Fronius Primo GEN24 10.0 Plus - AC input;output data

Fronius Primo GEN24 10.0 Plus
208 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DC input data battery
Max. voltage 455 V
Min. voltage 150 V
Max. current 22 A
Max. output 8000 W
DC inputs 1
AC input/output data
Nominal output power (P
nom
) 8000 W
Max. output power 8000 W
Rated apparent power 8000 W
Nominal grid voltage 1 ~ NPE 220V / 230V / 240 V
Min. grid voltage
155 V
1)
Max. grid voltage
270 V
1)
Max. output current 45.45 A
Current (inrush)
6)
20 A / 1.3 ms
Nominal frequency
50 / 60 Hz
1)
Nominal frequency for Full Backup
53 / 63 Hz
1)
Initial short circuit alternating cur-
rent / phase I
K
45.5 A
Total harmonic distortion < 3%
Power factor cos phi
2)
0.8 - 1 (adjustable)
Max. permitted mains impedance Z
max
at PCC
4)
None
Maximum output fault current / dura-
tion
29 A / 3 ms
AC output data PV Point
Max. output power 4133 W (for 5 s)
Rated power 3000 W
Nominal output current 13 A
Nominal grid voltage 1 ~ NPE 220 V / 230 V / 240 V
Nominal frequency
53 / 63 Hz
1)
Switching time < 90 s
Power factor cos phi
2)
0 - 1
AC output data Full Backup
Max. output power 11,024 W (for 5 s)
Rated power 8000 W
Nominal output current 34.8 A
171