AC output data Full Backup
Nominal grid voltage
1 ~ NPE 220 V
1 ~ NPE 230 V
1 ~ NPE 240 V
Nominal frequency for Full Backup
53 / 63 Hz
1)
Switching time < 90 s
Power factor cos phi
2)
0 - 1
General data
Maximum efficiency 97.4%
European efficiency (U
mpp nom
) 96.9%
European efficiency (U
mpp max
) 96.4%
European efficiency (U
mpp min
) 96.5%
Self-consumption at night 9 W
Cooling Controlled forced-air ventilation
Protection class IP 66
Dimensions H x W x D 595 × 529 × 180 mm
Weight 23.5 kg
Inverter topology Non-insulated transformerless
Permitted ambient temperature -40 °C - +60° C
Permissible humidity 0 - 100% (incl. condensation)
EMC emission class B
DC/AC overvoltage category
(in accordance with IEC 62109-1)
2 / 3
Pollution degree 2
Sound pressure 47 dB(A) (ref. 20µPa)
Safety class (according to IEC62103) 1
Protection devices
DC isolation measurement
11)
Warning / shutdown at R
ISO
<
100 kOHM
Overload performance Operating point shift, power limiter
DC disconnector Integrated
RCMU
11)
Integrated
RCMU classification The software class of the safety plat-
form(s) is specified as a class B con-
trol function (single channel with peri-
odic self-test) according to IEC60730
Annex H.
Active anti-islanding method Frequency conversion method
AFCI Integrated
172