Quick guide PV Point & PV Point Comfort 1515
4.2 PV Point Comfort
As the PV Point Comfort also supplies the phase in mains parallel operation, the circuit or socket must
also be protected with a 13A miniature circuit breaker in addition to the RCD (type A 30 mA). There
is a space-saving solution for this from ABB with the article designation "ABB DS301CC13A30".
Of course, any other combination of RCD and circuit breaker that meets the technical requirements can
also be used.
If, for example, a circuit is supplied, the existing 16A MCB in the main distribution board can also be
used. In backup power mode, however, a maximum of 13A is made available. If the backup power load
exceeds 13A, backup power operation stops.