Section 6 Parameter Settings
77 FT722 & FT742 (RS485) FF & PM Sensors User Manual
6.4.20 OS: Set or Query Overspeed Warning Scheme
Command
Parameter
OS
Command
Syntax
SET Sensor:
$<listenderID>,OS<mode>*<checksum><cr><lf>
$aa,OSm*hh<cr><lf>
QUERY Sensor:
$<listenerID>,OS?*<checksum><cr><lf>
$aa,OS?*hh<cr><lf>
Sensor output:
$<talkerID>,OS=<mode>*<checksum><cr><lf>
$aa,OS=m*hh
Parameters
<Mode>
D Overspeed Warning Disabled
E Overspeed Warning Enabled
Examples
Example 1
Enable the Overspeed Warning scheme. Verify that the command has been accepted.
Message
Comment
$01,OSE*//<cr><lf>
Enable the scheme
$01,OS?*//<cr><lf>
Query Overspeed Warning scheme
$WI,OS=E*56<cr><lf>
Sensor response
Example 2
Disable the Overspeed Warning scheme. Verify that the command has been accepted.
Message
Comment
$01,OSD*//<cr><lf>
Disable the scheme
$01,OS?*//<cr><lf>
Query Overspeed Warning scheme
$WI,OS=D*57<cr><lf>
Sensor response
Description
Use this command to query, enable or disable the Overspeed Warning Scheme (See
Section 2.7).