EasyManua.ls Logo

FTS MAXI-COOL - Selecting a Process Fluid

FTS MAXI-COOL
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Startup
Maxi-Cool
6 Rev 007, 04/12
© SP Scientific 2012
Selecting a Process Fluid
This recirculator is designed for operation with a host of industry standard fluids. The
fluid you choose will depend on what temperature range is required. Ethylene Glycol
and water (60/40 mix) is an inexpensive and readily available fluid for 25°C to +60°C.
For a fluid outside this temperature range, SP Scientific suggests using HT-30
Silicone Oil for 60°C to +100°C.
There are other fluids available, but to avoid potential application problems and to
speed troubleshooting; it is suggested that one of the fluids mentioned above be used.
DO NOT USE AUTOMOTIVE ANTI-FREEZE (it contains clotting agents). If for some
reason one of the above fluids is not suitable, and you select a different one, be sure
that it has a viscosity of less than 20 centistokes over the full temperature range of the
unit.
Note: All of the above mentioned fluids have viscosity of less than 20 centistokes across their
useable temperature ranges.
Since most systems have capability to achieve temperatures below 0°C, water should
not be used as a process.
Fluid
Temperature
Range (°C)
Flammability
Toxicity
Dielectric
Ethylene Glycol/Water (60/40 mix)
-25 / +60
Low
Low
Low
HT-30 Silicone Oil (Recommended)
-60 / +100
Low
Very Low
High