viii
Conformity to the Low Voltage Directive in the EU (Continued)
10. The inverter has been tested according to IEC/EN 61800-5-1 Short-circuit Test under the following
conditions.
Short-circuit current in the supply: 10,000 A
480V or below (400V class series inverters)
11. Use this inverter at the following power supply system.
L1
L2
L3
PEN
L1/R
L2/S
L3/T
G
Inverter
TN-C system
Power supply
L1
L2
L3
N
L1/R
L2/S
L3/T
Power Supply
TN-S system
PE
G
Inverter
L1
L2
L3
N
L1/R
L2/S
L3/T
Power supply
IT system *1)
G
Inverter
L1
L2
L3
N
L1/R
L2/S
L3/T
Power supply
TT system
(Earthed neutral)
G
Inverter
*1 Use this inverter at the following IT system.
Non-earthed (isolated from earth) IT
system
Can be used.
In this case the insulation between the control interface
and the main circuit of the inverter is basic insulation.
Thus do not connect SELV circuit from external controller
directly (make connection using a supplementary
insulation.).
IT system which earthed neutral
by an impedance
Corner earthed / Phase-earthed IT
system by an impedance
Cannot be used