Conformity with Canadian standards and U.S. standards (Continued)
4. Use wires listed in CSA or UL.
Nominal applied motor (kW)
Inverter type
2
Main terminal
External braking resistor
*1
Control circuit
-]
[R0, T0] *1
Inverter
outputs
[U, V, W]
Inverter’s
grounding
[
G]
Three-phase 400 V
4.0
FRN0010LM2C-4
6
(13.3)
14
(2.1)
14
(2.1)
18
(0.8)
18
(0.8)
-
5.5
FRN0015LM2C-4
(3.3)
7.5
FRN0019LM2C-4
10
11
FRN0025LM2C-4
(8.4)
15
FRN0032LM2C-4
8
applied motor (kW)
Inverter type
Copper wire size AWG (mm
2
)
Main power input
DC reactor connection
[P2,P3] *1
With
DCR
Without
DCR
With
DCR
Without
DCR
Three-phase 400 V
4.0 FRN0010LM2C-4
14
(2.1)
12
14
12
5.5 FRN0015LM2C-4
10
(5.3)
12
10
7.5 FRN0019LM2C-4
12
10
8
11 FRN0025LM2C-4
10
(5.3)
8
(8.4)
8
(8.4)
-
15 FRN0032LM2C-4
8
6
6
(13.3)
Note: A box () replaces an alphabetic letter depending on the shipping destination.
Shipping destination: E (Europe)
*1 Use Cu wire only. The wire size for main circuits is for the 75 °C only.