36
Chapter 11 TROUBLESHOOTING
If any problem or error occurs during DeviceNet communication, follow the troubleshooting procedures given
below.
No Phenomenon/Symptom Probable Causes
1
None of the LEDs on the
option would light.
• No 24 VDC power supply is connected to this option.
• The option is faulty.
2
er4
alarm cannot be reset
(The MS LED lights in red).
• The option is not properly mounted.
• The option connection cable is not connected.
• The option is faulty.
3
The NS LED lights in red.
(
er5
alarm cannot be reset.)
• The same node address is double assigned in DeviceNet.
• There is a mismatch in baud (data) rate.
• The network power (24 V) is not properly supplied.
• Cabling for DeviceNet communications is not properly done.
• The inverter and the option have not been powered OFF and
then ON after modifying the DIP switch settings.
4
The NS LED blinks in red.
(
er5
alarm has occurred.)
• The cable was broken during communication.
• The I/O scan interval is too short.
5 The NS LED would not light.
• The node address for the option is improper.
• The cable for DeviceNet communications was broken.
6
The NS LED keeps blinking in
green and does not come to
stay on in green.
• The master does not request a connection.
• The I/O scan interval has been set to be too short at the start of
communication.
• The I/O area is invalidly mapped.
• There is no I/O connection.
7
Even though the NS LED
lights in green, the settings for
run command or speed
command cannot be
validated.
• Neither NetCtrl nor NetRef is set to "1."
• On the inverter, the higher-priority run command or speed
command is enabled.
• There is a mistake in the selection of I/O Assembly Instances.
• The inverter and the option have not been powered OFF and
then ON after modifying the o31 data.
8
Although the speed command
has been validated, the actual
speed is different from it.
• Refer to the FRENIC-Multi Instruction Manual
(INR-SI47-1094-E), Section 6.2.1 "Motor is running abnormally."