Conformity to UL standards and Canadian standards (cUL certification) (Continued)
7. Install UL/CSA certified circuit breaker rated 240 V or more for 230 V input, 480 V or more
for 460 V input between the power supply and the inverter, referring to the table below.
Standard type
Required torque
Ib-in (N·m)
Wire size
AWG or kcmil (mm
2
)
Power
supply
voltage
Inverter type
Main
terminal
Control circuit
Main
terminal
Control circuit
Circuit breaker (A)
FRNF12E1S-2U 5
FRNF25E1S-2U 5
FRNF50E1S-2U 5
FRN001E1S-2U
10.6 (1.2)
10
FRN002E1S-2U 15
FRN003E1S-2U
14
20
FRN005E1S-2U
15.9 (1.8)
10 30
FRN007E1S-2U 8 50
FRN010E1S-2U
33.6 (3.8)
75
FRN015E1S-2U
6
100
Three-phase 230 V
FRN020E1S-2U
51.3 (5.8)
4.4
(0.5)
4
20
(0.5)
125
FRNF50E1S-4U 5
FRN001E1S-4U 5
FRN002E1S-4U 10
FRN003E1S-4U 15
FRN005E1S-4U
15.9 (1.8) 14
20
FRN007E1S-4U 12 30
FRN010E1S-4U
33.6 (3.8)
40
FRN015E1S-4U
10
50
Three-phase 460 V
FRN020E1S-4U
51.3 (5.8)
3.5
(0.4)
8
20
(0.5)
60
FRNF12E1S-7U 5
FRNF25E1S-7U 5
FRNF50E1S-7U 10
FRN001E1S-7U
10.6
(1.2)
14
15
FRN002E1S-7U 12 20
Single-phase 230 V
FRN003E1S-7U
15.9
(1.8)
4.4
(0.5)
10
20
(0.5)
30