When mounting two or more inverters 
Horizontal layout is recommended when two or more 
inverters are to be installed in the same unit or panel. If it is 
necessary to mount the inverters vertically, install a partition 
plate or the like between the inverters so that any heat 
radiating from an inverter will not affect the one/s above. As 
long as the ambient temperature is 40°C (104qF) or lower, 
inverters can be mounted side-by-side without any gap 
between them (only for inverters with a capacity of less than 
7.5 HP). 
 When employing external cooling 
At the shipment time, the inverter is set up for mount inside 
your equipment or panel so that cooling is done all internally.
To improve cooling efficiently, you can take the heat sink out 
of the equipment or the panel (as shown on the right) so that 
cooling is done both internally and externally (this is called 
"external cooling"). 
In external cooling, the heat sink, which dissipates about 
70% of the total heat (total loss) generated into air, is situated 
outside the equipment or the panel. As a result, much less 
heat is radiated inside the equipment or the panel. 
To take advantage of external cooling, you need to use the 
external cooling attachment option for inverters with a 
capacity of 7.5 HP or above. 
In an environment with high humidity or a lot of fibrous dust, 
however, do not use external cooling in an environment with 
high humidity or a lot of fibrous dust, which tends to clog the 
heat sink. 
 For details, refer to the Mounting Adapter for 
External Cooling "PB-F1/E1" Installation Manual. 
50°C
(122°F)"
Figure 2.2  External Cooling 
Prevent lint, paper fibers, sawdust, dust, metallic chips, or other foreign materials from getting 
into the inverter or from accumulating on the heat sink. 
This may result in a fire or accident.