3-10
Setting up the primary frequency command with   and   keys under PID dancer control
When function code F01 is set to "0" (  / 
keys on keypad) and frequency command 1 is 
selected as a primary frequency command (when disabling the frequency setting command via 
communications link and multi-frequency command), switching the LED monitor to the speed 
monitor in Running mode enables you to modify the frequency command with the 
 / 
keys.  
In Programming or Alarm mode, the 
 /  keys are disabled to modify the frequency command. 
You need to switch to Running mode.  
Table 3.7 lists the combinations of the commands and the figure illustrates how the primary 
frequency command 
entered via the keypad is translated to the final frequency command  .
The setting procedure is the same as that for setting of a usual frequency command. 
Table 3.7  Primary Frequency Command Specified with   /   Keys and Requirements 
PID control 
(Mode
selection) 
J01
LED
monitor
E43
Frequency
command
1 F01 
Multi- 
frequency
SS2
Multi- 
frequency
SS1
Communi-
cations
link
operation
LE
Cancel PID
control
Hz/PID
Pressing
 / 
keys controls: 
OFF
(PID
enabled)
Final frequency 
command modified 
by PID output 
0 OFF OFF OFF 
ON
(PID
disabled)
Keypad primary 
command 
(Frequency) 
OFF
(PID
enabled)
Final frequency 
command modified 
by PID output 
3 0 
Other than the above 
ON
(PID
disabled)
Current primary 
command 
(Frequency)