3-17
Basic key operation
To monitor the running status on the drive monitor, set function code E52 to "2" (Full-menu mode)
beforehand.
(1) Turn the inverter ON. It automatically enters Running mode. In that mode, press the
key to
switch to Programming mode. The function selection menu appears.
(2) Use the
and keys to display "Drive Monitoring" (
QRG
).
(3) Press the
key to proceed to a list of monitoring items (e.g.
A
).
(4) Use the
and keys to display the desired monitoring item, then press the key.
The running status information for the selected item appears.
(5) Press the
key to return to a list of monitoring items. Press the key again to return to the
menu.
Table 3.12 Drive Monitor Display Items
LED
monitor
shows:
Item Unit Description
A
Output
frequency
Hz
Output frequency before slip compensation
A
Output
frequency
Hz
Output frequency after slip compensation
A
Output current
A
Output current
A
Output voltage
V
Output voltage
A
Calculated
torque
%
Calculated output torque of the motor in %
A
Reference
frequency
Hz
Frequency specified by a frequency command
A
Rotational
direction
N/A
Rotational direction being outputted
H
: forward,
T
: reverse,
: stop
A
Running
status
N/A
Running status in hexadecimal format
Refer to " Displaying running status
" on the next page.
120
Display value = (Output frequency Hz) u
(Function code P01)
A
Motor speed
r/min
For motor 2, read P01 as A15.
A
Load shaft
speed
or
Line speed
r/min
m/min
Display value = (Output frequency Hz) u (Function code E50)
The 7-segment letters
appear for 10000 (r/min) or more. If
appear, decrease function code E50 data so that the LED
monitor displays 9999 or below, referring to the above equation.
A
PID command
N/A
Virtual physical value (e.g., temperature or pressure) of the object to
be controlled, which is converted from the PID command using
function code E40 and E41 data (PID display coefficients A and B)
Display value = (PID command) u (Coefficient A - B) + B
If PID control is disabled, "
" appears.
A
PID feedback
amount
N/A
Virtual physical value (e.g., temperature or pressure) of the object to
be controlled, which is converted from the PID command using
function code E40 and E41 data (PID display coefficients A and B)
Display value = (PID feedback amount) u (Coefficient A - B) + B
If PID control is disabled, "
" appears.
A
Torque limit
value
% Driving torque limit value A (based on motor rated torque)
A
Torque limit
value
% Braking torque limit value B (based on motor rated torque)