vii
Conformity to the Low Voltage Directive in the EU (Continued)
10. Use wires listed in EN60204 Appendix C.
Recommended wire size (mm
2
)
*1
Rated current (A)
of
MCCB or RCD/GFCI
*2
Main circuit
power input
[L1/R, L2/S , L3/T]
[L1/L, L2/N]
Grounding [
G]
Power
supply voltage
Applied
motor
rating
(HP)
Inverter type
w/ DCR
*3
w/o DCR
w/ DCR
*3
w/o DCR
*2
Inverter
output
[U, V, W ]
*2
DCR
[P1,
P (+)]
Braking
resistor
[P (+),
DB]
Control
circuit
(30A,
30B,
30C)
1/8 FRNF12E1
ع
-2U
1/4 FRNF25E1
ع
-2U
1/2 FRNF50E1
ع
-2U
5
1 FRN001E1
ع
-2U
5
10
2 FRN002E1
ع
-2U 15
3 FRN003E1
ع
-2U
10
20
2.5
5 FRN005E1
ع
-2U 20 30
2.5
4.0
2.5 2.5
7.5 FRN007E1
ع
-2U 30 50 4.0 6.0 4.0 4.0
10 FRN010E1
ع
-2U 40 75 6.0 10 6.0 6.0
15 FRN015E1
ع
-2U 50 100 10 16 10 16
Three-phase
230 V
20 FRN020E1
ع
-2U 75 125 16 25 16 25
0.5
1/2 FRNF50E1
ع
-4U
1 FRN001E1
ع
-4U
5
2 FRN002E1
ع
-4U
5
10
3 FRN003E1
ع
-4U 15
5 FRN005E1
ع
-4U
10
20
7.5 FRN007E1
ع
-4U 15 30
2.5
10 FRN010E1
ع
-4U 20 40
2.5
4.0
2.5 2.5
15 FRN015E1
ع
-4U 30 50 4.0 6.0 4.0 4.0
Three-phase
460 V
20 FRN020E1
ع
-4U 40 60 6.0 10 6.0 6.0
0.5
1/8 FRNF12E1
ع
-7U
1/4 FRNF25E1
ع
-7U
5
1/2 FRNF50E1
ع
-7U
5
10
1 FRN001E1
ع
-7U 10 15
2.5
2 FRN002E1
ع
-7U 15 20
2.5
4.0
2.5
Single-phase
230 V
3 FRN003E1
ع
-7U 20 30 4.0 6.0
2.5
4.0
0.5
MCCB: Molded case circuit breaker RCD: Residual-current-operated protective device
GFCI: Ground fault circuit interrupter
Note 1) A box (
) in the above table replaces S (Standard type) or E (EMC filter built-in type)
depending on the product specifications
.
*1 The frame size and model of the MCCB or RCD/GFCI (with overcurrent protection) will vary,
depending on the power transformer capacity. Refer to the related technical documentation for
details.
*2 The recommended wire size for main circuits is for the 70qC(158qF) 600 V PVC wires used at an
ambient temperature of 40qC(104qF).
*3 In the case of no DC reactor, the wire sizes are determined on the basis of the effective input
current calculated under the condition that the power supply capacity and impedance are 500 kVA
and 5%, respectively.