17
–
Operation/Standby mode
SEL
Press for about
3 sec.
SEL
Press for about
2 sec.
(Returns to SV indication)
SV
C1
SEL
C2
AL1
AL2
Control output status
Alarm status
SV indication lamp is lit when the set value is shown.
· Some parameters may not be
displayed on the screen, depending
upon the types.
Parameter
Proportional band
Description of contents
Default
setting
Remarks
P
I
D
TC
TC2
CooL
db
P-SU
P-dP
ALM1
ALM2
HYS
Hysteresis for ON/OFF control
Cycle time (control output 2)
Deadband/overlap
Proportional band
coefficient on cooling side
Input type code
Lower limit of input range
As ordered
As ordered
P-n2
P-SL
As ordered
As ordered
0/5
0/9
5.0
Derivative action time
60.0
Integral time (reset)
240
Cycle time (control output 1)
Setting types of alarm action (Setting range: 0 to 34)
Setting of decimal point
position
PVOF
0
PV offset
Type of alarm 1
Upper limit of input range
Type of alarm 2
1
30/2 Note 2
30/2
1.0
0.0
PTn
1
Selects the ramp/soak execute type.
1: Executes 1st to 4th segment.
2. Executes 5th to 8th segment.
3. Executes 1st to 8th segment.
Ramp/soak execute type
SV-1
to
SV-8
0%FS
Sets the target SV for each ramp segment.
(Setting range: 0 to 100%FS)
Ramp target SV-1 to SV-8
TM1r
to
TM8r
0.00
Sets the time for each ramp segment.
(Setting range: 0 to 99 hours and 59 minutes)
1st ramp segment time to
8th ramp segment time
TM1S
to
TM8S
0.00
Sets the time for each soak segment.
(Setting range: 0 to 99 hours and 59 minutes)
1st soak segment time to
8th soak segmentl time
STAT
-
Ramp/soak status
Shift the display of process value (PV).
(Setting range: -10 to 10%FS)
Displays the current Ramp/Soak status.
No setting can be made.
Setting range: 0.0 to 999.9%
ON/OFF control when "P" = 0
Setting range: 0 to 3200 sec.
No integral action when "I" = 0
Setting range: 0.0 to 999.9 sec.
No derivative action when "d" = 0
Sets cycle time of control output 1.
(Setting range: 1 to 150 sec)
Setting range: 0 to 50% FS
Sets cycle time of control output 2.
(Setting range: 1 to 150 sec)
Sets the proportional band coefficient on the cooling side.
(Setting range : 0.0 to 100.0)
ON/OFF control when "Cool" = 0
Shifts the output value on the cooling side.
(Setting range: -50.0 to 50.0%)
Lower limit of input range
(Setting range: -1999 to 9999)
Upper limit of input range
(Setting range: -1999 to 9999)
Type of input Table 1
(Page 4)
Table 2
(Page 4)
Table 2
Table 2
(Page 4)
Table 3
(Page 4)
Table 3
(Page 4)
Select a decimal point position of display.
(Setting range: 0 to 2)
. .
"1"
0 : No decimal point
"2"
CTrL
PID
Type of control algorithm.
(Setting range: PID, FUZZY, SELF)
Control algorithm
P-dF
Time constant of input filter
5.0
Time constant (Setting range: 0.0 to 900.0 sec.)
2nd block parameter
Parameter
display symbol
Note 2
Table 2
(Page 4)