16
–
5 Setting methods of temperature and parameters
Operation/Standby mode
SEL
Press for about
1 sec.
SEL
Press for about
2 sec.
(Returns to SV indication)
SV
C1
SEL
C2
AL1
AL2
Control output status
Alarm status
SV indication lamp is lit when the set value is shown.
· Some parameters may not be
displayed on the screen, depending
upon the types.
Parameter
display symbol
Parameter
Standby settings
Description of contents
Default
setting
Remarks
STbY
ProG
LACH
AT
TM-2
AL1
A1-L
A2-L
A2-H
LoC
TM-1 Timer 1 display
Timer 2 display
Alarm 1 low limit
set value
Alarm 1 set value
Alarm 1 high limit
set value
(appears only with alarm action type 1 to 10).
Setting range: Note 1
Alarm 2 set value
10
10
A1-H
AL2
10
10
0
Switches RUN or Standby of the control.
ON: Control standby (output: OFF, alarm: OFF)
OFF: Control RUN
OFF: stop, rUn: Start, HLd: status hold
0: Stop, 1: Standard AT start, 2: Low PV type AT start
OFF
Alarm latch cancel Releases alarm latch.
1: Alarm latch release
0
Ramp/soak control
OFF
Auto-tuning
Time display indicating the remaining time in the timer
mode.
(appears only with alarm action type 1 to 10).
Setting range: Note 1
(appears only with alarm action type 16 to 31).
Setting range: Note 1
Alarm 2 high limit
set value
(appears only with alarm action type 16 to 31).
Setting range: Note 1
Alarm 2 low limit
set value
Setting of key lock status. Key lock
10
0
10
10 Table 3
(Note 1)
Table 3
(Note 1)
Table 3
(Note 1)
Table 3
(Note 1)
Table 3
(Note 1)
Table 3
(Note 1)
10
All parameters
Front key
0
1
2
3
4
5
Comm-
unication
SV
Front key Comm-
unication
Note 1) Setting range : 0 to 100%FS (in case of absolute value alarm)
–100 to 100%FS (in case of deviation alarm)
Note 2) Never set “TC” / “TC2” = 0
1st block parameter
: Setting enable, : Setting disable