34
–
Parameter
:
[Table 2] Control output action code
(*) Outputs when Error Indication Group I.
Please refer to 8 (Error indications).
This is effective even in Standby mode.
Lower limit: OFF or 4mA or less
Upper limit: ON or 20mA or more
[Caution for dual output] (option)
(1) Parameter “I” and “D” can not be set separately.
(2) In case “P”=0 (ON/OFF control) for heating side, cooling side becomes ON/OFF control automatically.
(3) In case “Cool”=0.0, cooling side becomes ON/OFF control. And hysteresis is xed at 0.5%FS.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Single
(Control output 1)
Dual
Control output
1 and 2.
Heating/Cooling
Output 1
Reverse action
Direct action
Reverse action
Direct action
Reverse action
Direct action
Output 2
---
Direct action
Reverse action
Output 1
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Output 2
---
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Control output action Output at Burn-out*
Code
Output