39
–
Specication
Power voltage: 100 (-15%) to 240 (+10%), 50/60Hz
24V AC 50/60Hz, 24V DC
Power consumption: 6VA or less (100V AC), 8VA or less
(240V AC, 24V AC/24V DC)
Relay contact output: SPST contact, 220V AC/30V DC 3A
(resistive load)
SSR/SSC driving output*1: ON: 15V DC (12 to 16V DC)
(voltage pulse output) OFF: 0.5V DC or less
Maximum current: 20mA or less
Resistive load: 600Ω or more
4-20mA DC output*1: Allowable load resistor: 100 to 500Ω
Alarm output: Relay contact (SPST contact)
220V AC / 30V DC 1A (resistive load)
Communication function*2: Transmission system: Half-duplex bit serial start-
(RS-485 interface) stop synchronization
Transmission rate: 9600bps
Transmission protocol: In conformity to
Modbus RTU or Z-ASCII (PXR protocol)
Transmission distance: Up to 500m (Total length)
Connectable units: Up to 31units
Digital input: Number of input: 2 inputs MAX.
Input contact capacity: 5V, 2mA DC
Retransmission: 4 to 20mA DC
Allowable load resistor: 500Ω or less
Accuracy: ±0.3%FS (at 23ºC)
Altitude: ≤ 2000m
Transient overvoltage on mains power: ≤ 2500V
Operating ambient temperature: -10 to 50ºC
-10 to 45ºC (for mounting close together)
Operating ambient humidity: 90%RH or less (no condensation)
Preservation temperature: -20 to 60ºC
Voltage Maximum current
SSR/SSC driving output
Allowable load
resistance for 4 to
20mA DC output
*1 : The following table shows the difference of outputs among other micro-controller X series models.
*2 : For the connection with a PC, communication converter is required.
PXR3
PXR4
PXV3
PXV/W/Z
15V DC 20mA
24V DC 20mA
5.5V DC 20mA
24V DC 60mA
100 to 500
600 or less
600 or less
600 or less